YXKS-500-2 6KV Ultra Efficiency Water Cooling 3 Phase Asynchronous Motor

Ultra Efficiency Water Cooling 3-Phase Asynchronous Motor YXKS

YXKS-500-2 6KV Ultra Efficiency Water Cooling 3 Phase Asynchronous Motor

Frame Size

H500mm

No. of Poles

2P

Rated Power

1250KW~1800KW

Rated Voltage

6KV

Rated Frequency

50/60HZ

Insulation

155 (F) Grade

Protection Grade

IP55

Mounting Type

IM B3

Cooling Method

IC81W

Duty

S1

Connection

Y

Vibration

≤2.3mm/s

Altitude

≤1000m

Ambient temperature

-15℃ ~ +40℃

Place of Origin

Xi’an, China

Brand name

SIMO MOTOR

Humidity

Average monthly peak relative humidity is 90%


*Note: Motors can be customized according to customer’s requirements.

    Motor Description

    • YXKS series ultra-efficiency water cooling3 phase asynchronous motor shall be operated when the altitude does not exceed 1000m, the motor has been processed with anticorona measures if the altitude is over 1000m. Besides, the ambient air temperature shall not exceed 40℃, and the ambient air temperature shall not be less than -15℃ except the following motors:
      a)    Rated output is more than 3300kW(or KVA)/1000r/min;
      b)    Rated output is less than 600W(or VA);
      c)    Sliding bearing;
      d)    Regard water as primary or secondary cooling medium.

      The lowest ambient air temperature for these motors shall not below 0℃.

      Cooling water temperature: for the motors adopting air-water cooling (IC81W), the water temperature at the entrance of motor cooler shall not be higher than +25℃ or be lower than +5℃.

      Cooling water pressure: for the motors adopting air-water cooling (IC81W), the cooling water pressure of motor cooler shall be selected according to the indication of cooler nameplate.

      The monthly average maximum relative humidity is 90% in the wettest month in the operating place; Meanwhile, monthly average minimum temperature shall not be higher than 25℃ in such month. When ambient air temperature and elevation are not in conformity with above regulations, the temperature rise of motors can be corrected pursuant to the provisions of GB 755.

      Special field operating conditions shall be stated upon ordering and motor with special purpose shall be selected, such as: W—outdoor slight corrosion prevention type, WF1—outdoor medium corrosion prevention type, WF2—outdoor strong corrosion prevention type, F1—indoor medium corrosion prevention type, F2—indoor strong corrosion prevention type, WTH—outdoor wet tropical zone, WTA—outdoor dry tropical zone and G—high altitude type, etc.

    Outline Dimensions

    YXKS-500-4y2e

    Motor Parameters

    Type Rated Power kW Rated Current A Rated Speed r/min Eff. % Power Factor Cosφ Locked Torque Locked Current Max. Torque Load moment of inertia Kg.m2 Weight Kg
    Rated Torque Rated Current Rated Torque
    YXKS5002-2 1250 142.2 2980 96.1 0.88 0.6 7 1.8 67 5510
    YXKS5003-2 1400 159.1 2980 96.2 0.88 0.6 7 1.8 73 5600
    YXKS5004-2 1600 181.7 2980 96.3 0.88 0.6 7 1.8 80 5720
    YXKS5005-2 1800 204.4 2980 96.3 0.88 0.6 7 1.8 86 5850

    Application

    description1