English
Leave Your Message
Reactive Capacitance Compensation Cabinet

High/Low Voltage Complete Plant

Reactive Capacitance Compensation Cabinet

In industrial and agricultural production, there are a large number of reactive power equipment, which will reduce the voltage of power system, increase power loss, and then affect power quality. Therefore, the corresponding reactive power compensation device came into being; GGJ low-voltage reactive power compensation cabinet is specially produced for low-voltage reactive capacitance compensation cabinet.

The device is developed according to the requirements of IEC439-1 “Low-voltage switchgear box control equipment”, GB7251.1-2[11005 “Low-voltage switchgear box control equipment” and GB/T15576-2008 “Low-voltage switchgear box reactive power compensation device”.

    Technical parameters

    Rated voltage 380VAC3-
    Rated insulation voltage 660VAC3-
    Rated frequency 50HZ or 60HZ
    Compensation method three-phase compensation and single-phase compensation are combined.
    Compensation capacity 420Kvar~60Kvar
    Compensation method cyclic switching, coding switching, fuzzy control automatic switching
    The fastest response time ≤20ms
    Cabinet size 1000*1000*2200 (mm)
    Protection class IP20

    Operation environment

    • 1. The ambient air temperature is not higher than+40°C and not lower than-5°C. The average temperature within 24 hours shall not be higher than+35°C.
      2. Indoor installation and use, the altitude of the place of use shall not exceed 2000 meters.
      3. The relative humidity of ambient air shall not exceed 50% at the highest temperature of+40°C, and a larger relative temperature is allowed at the lower temperature. (for example, 90% at +20°C) The influence of condensation that may occasionally occur due to temperature change should be considered.
      4. When the equipment is installed, the inclination from the vertical plane shall not exceed 5%.
      5. The equipment should be installed in a place where there is no violent vibration and where the electrical components are not corroded.
      6. Users can negotiate with the manufacturer to solve special requirements.

    Application

    description1