English
Leave Your Message
MaxWell-H High-voltage Variable Frequency Drive

High/Low Voltage Inverter

MaxWell-H High-voltage Variable Frequency Drive

Power Input

Input voltage

Voltage class 6KV or 10KV, output rated power is output when voltage fluctuation range

is within -10%~+10%. 

Output power is derated within -45%~-10%.

Input frequency

50Hz,frequency fluctuation range -10%~+10%

Input current harmonic

THDI≤4%, meeting international standard IEEE 519-2014 and national standard GB/T

14549-93 power quality standard

Input power factor

Up to 0.96


    Parameters

    Power Input
    Input voltage Voltage class 6KV or 10KV, output rated power is output when voltage fluctuation range is within -10%~+10%. Output power is derated within -45%~-10%.
    Input frequency 50Hz,frequency fluctuation range -10%~+10%
    Input current harmonic THDI≤4%, meeting international standard IEEE 519-2014 and national standard GB/T 14549-93 power quality standard
    Input power factor Up to 0.96
    Power output
    Output voltage range 0~6KV or 0~10KV
    Output frequency 0-120Hz
    System efficiency Up to 97%
    Output overload Work for a long time with the load less than 105%, and inverse time protection enables within 110% ~ 160%.
    Output current harmonic THDI≤4%, meeting international standard IEEE 519-2014 and national standard GB/T 14549-93 power quality standard
    Control Mode
    Control mode V/F, VC control without speed sensor, VC control with speed sensor
    Acceleration/deceleration time 0.1-3600S
    Frequency resolution
    Frequency accuracy Digital setting ±0.01% max. frequency, analogue setting ±0.2% x set max. frequency
    Speed resolution Digital setting 0.01Hz, analogue setting 0.1 x set maximum frequency
    Speed accuracy ±0.5%
    Speed fluctuation ±0.3%
    Starting torque Larger than120%
    Excitation braking Braking time 1-600S, starting frequency 0-30Hz, braking current 0-150% of rated current
    DC braking Braking time 0-600S, starting frequency 0-50Hz, braking current 0-100% of rated current Larger than120%
    Automatic voltage regulation When the input voltage varies within -10% to +10%, the output voltage can be kept constant automatically and the rated output voltage fluctuates by no more than ±3%.
    Machine parameters
    Cooling method Air cooling
    Protection class IP30
    Insulation class for phase shifting transformers Class H (180℃)
    Local operation mode Touch screen
    Auxiliary power supply ≥20 kVA
    Environmental adaptability
    Ambient operating temperature 0~+40℃ It can start directly at -15°C, and capacity derates for use at 40°C to 55°
    Ambient storage temperature -40℃~+70℃
    Ambient transport temperature -40℃~+70℃
    Relative humidity 5%-95%RH no condensation
    Altitude less than 2000m
    Installation site Indoor
    Contamination level Contamination level 3 and occasional conductive contaminants are allowed
    User interface
    Analogue input 3
    Analogue output 2
    Communication interface 2
    High voltage circuit breaker control 1
    Code plate interface 1
    Relay type dry contact output 6
    Transistorised dry contact output 4
    Multi-functional terminal input 8
    Power supply interface 380V AC

    Description

    • SIMO’s MAXWELL H series Variable Frequency Drives are versatile devices used to optimize motor performance, enhance energy efficiency, and provide fine-tuned control in a wide range of applications.
      This product can be used in a wide range of applications and can meet the requirements for variable frequency speed control and energy saving of high voltage motors in a variety of complex situations.

    Specifications

    MaxWell 6kV series
    Models

    Motor Power

    (kW)
    Rated output current  (A) Weight (kg) Dimensions (mm)
    MaxWell-H0185-06 185 23 2030 1850*1770*2350
    MaxWell-H0200-06 200 25 2049
    MaxWell-H0220-06 220 27 2073
    MaxWell-H0250-06 250 31 2109
    MaxWell-H0280-06 280 34 2145
    MaxWell-H0315-06 315 38 2187
    MaxWell-H0355-06 355 43 2236
    MaxWell-H0400-06 400 48 2363
    MaxWell-H0450-06 450 54 2385
    MaxWell-H0500-06 500 60 2410
    MaxWell-H0560-06 560 67 2479
    MaxWell-H0630-06 630 75 2609
    MaxWell-H0710-06 710 85 2664
    MaxWell-H0800-06 800 94 2773
    MaxWell-H0900-06 900 106 2894
    MaxWell-H1000-06 1000 117 3060
    MaxWell-H1120-06 1120 131 3268
    MaxWell-H1250-06 1250 144 3502
    MaxWell-H1400-06 1400 161 3577
    MaxWell 10kV series
    Models Motor Power (kW) Rated output current (A) Weight (kg) Dimensions (mm)
    MaxWell-H0220-10 220 17 2163 1850*1770*2350
    MaxWell-H0250-10 250 19 2202
    MaxWell-H0280-10 280 21 2241
    MaxWell-H0315-10 315 24 2286
    MaxWell-H0355-10 355 26 2338
    MaxWell-H0400-10 400 29 2475
    MaxWell-H0450-10 450 33 2505
    MaxWell-H0500-10 500 36 2526
    MaxWell-H0560-10 560 40 2600
    MaxWell-H0630-10 630 45 2740
    MaxWell-H0710-10 710 51 2799
    MaxWell-H0800-10 800 56 2916
    MaxWell-H0900-10 900 63 3046
    MaxWell-H1000-10 1000 70 3225
    MaxWell-H1120-10 1120 79 3848
    MaxWell-H1250-10 1250 87 4100 2625*1895*2470
    MaxWell-H1400-10 1400 97 4180
    MaxWell-H1600-10 1600 110 4610
    MaxWell-H1800-10 1800 124 4990
    MaxWell-H2000-10 2000 138 5180
    MaxWell-H2250-10 2250 154 5573

    Application

    description1